What is the Advantage and Disadvantage of Industrial Cooling System Manufacturers

26 May.,2025

 

Pros and Cons of Cooling System Water Sources and Treatment ...

Cooling towers play a critical role in both indoor climate control and process cooling systems. Ensuring a high-quality water supply for these components enhances their efficiency, extends their lifespan, and simplifies maintenance.

Click here to get more.

Municipal-supplied or well water has historically been the most common source of makeup water for evaporative cooling systems. However, concerns related to water scarcity and increasing water costs are leading some building owners, engineers, and facilities managers to seek alternative sources of water and treatment for their evaporatively cooled systems. Options include gray water reuse, rainwater capture, makeup water pretreatment systems, and blowdown reuse systems.

The various makeup water sources and treatment systems have potential advantages and disadvantages. What’s best for a specific application depends on the available makeup water source(s), the evaporative cooling equipment being used, and the process that the cooling system serves. This article addresses the water quality of various makeup sources and the pros and cons of some treatment systems.

EVAPCO’s Water Analytical Services, in Taneytown, Md., was established to analyze makeup and recirculating water associated with evaporatively cooled systems. An example of a makeup water report can be seen below:

Analyzing site-specific makeup water is a good first step for contractors, engineers, and facilities managers interested in maximizing equipment service life and water efficiency. This type of analysis provides an understanding of what type of treatment program might be required to optimize operating cycles of concentration in their evaporative system. Further, the makeup water analysis can help determine whether upgrading the materials of construction from galvanized steel to 304 or 316 stainless steel can help save water.

One of the factors to consider while weighing makeup water treatment options is the source of the water. Various sources present different benefits and challenges.

Municipal Water

Municipal (city) water supply is the most common makeup water source for evaporative units in hospitals, hotels, schools, data centers, and commercial buildings.

Pros: Typically, municipal water sources offer consistent water quality, which simplifies the water treatment program. It’s also a very convenient source of makeup water because city water is already piped to the building.

Cons: City water can be more costly than other makeup water alternatives, and there may be connection fees. Also, the local municipal water treatment plant may limit the amount of water that’s available to new facilities. 

Well Water

Well water can also be used to supply makeup water to an evaporative unit. This is more common at production facilities or in rural areas.

Pros: Generally, well water is less expensive than city water and connection fees are reduced.

Cons: Well water tends to have higher alkalinity and hardness levels than city water, and this can limit water efficiency do to greater scale formation potential. Well water may also contain elevated levels of iron, manganese, or silica concentrations, and may require disinfection or filtration use in the facility or process.

Gray Water

Gray water may also be referred to as reclaimed, recycled, or “purple pipe” water.

Pros: Gray water is generally less expensive than local municipal water, and may be available in areas that do not have a surplus of municipal water for new facilities or systems.

Cons: Quality of water varies more broadly compared to other sources, making the site’s ongoing water treatment more complicated. Gray water typically contains higher levels of ammonia, nitrate, phosphate, and suspended solids, which can impact corrosion or deposition concerns. 

Condensate Water

Condensate recycling from air handler units can be an option for facilities that utilize large volumes of outside air in the HVAC system. Cold condensate can be a source of pure water.

Pros: Condensate water is a source of low-conductivity water that would otherwise be sent to drain.

Cons: Requires piping and storage system to blend in with another makeup water source. It can also be corrosive to system metallurgy if not blended consistently with another source of water.

Rainwater

Harvesting rainwater can provide an additional source of makeup water in areas with sufficient rainfall. Rainwater is captured in a tank, filtered, treated, and blended as a supplemental makeup water source.

Pros: It’s “free” once the infrastructure is in place, and typically has low mineral content, making it low conductivity water for blending.

Cons: Low concentrations of hardness and alkalinity in rainwater make it more corrosive than some other sources, so blending consistently is critical. Rainwater also requires pre-filtration to reduce suspended solids before entering the holding tank. Holding tanks may require biocide to control microbiological activity.

Regardless of the water source used to supply makeup water for an evaporative cooling system, some level of pretreatment is required.

Pretreatment

Geographies with poor makeup water quality requiring low operating cycles of concentration (COC) can often benefit from the addition of a pretreatment system. Pretreatment systems can improve the quality of city, well, or gray water before it is used as makeup for an evaporatively cooled system.

Using a pretreatment system to reduce the water’s dissolved ion concentration and corresponding conductivity may allow a facility to safely increase the operating cycles of concentration. Higher operating cycles of concentration lowers blowdown water volume, which can reduce total water usage (blowdown equation shown below).

The goal of cooling water treatment programs is to create a balance between minimizing corrosion and scale potential and water efficiency (increasing operating COC) in the system. There are several different pretreatment systems that have been applied to evaporative cooling systems. Additionally, pH control (acid feed) has been utilized to reduce scaling potential to increase operating cycles of concentration. Pros and cons for several of these approaches are summarized below.

Sodium Zeolite Softener

Some vendors recommend “soft water” to minimize scale potential and increase operating cycles of concentration. Softeners exchange calcium and magnesium hardness with sodium. Using split-stream softening to reduce total hardness can be an appropriate option when hardness is the primary limiter of cycles of concentration. Makeup water sources high in alkalinity, chloride, silica, or sulfate limit the effectiveness of softeners to increase operating cycles of concentration and save water.

In its operations and maintenance manual, EVAPCO recommends a minimum of 50 ppm cycled calcium hardness (as CaCO3) in the recirculating water to help protect system metallurgy from corrosion. Leading equipment manufacturers do not recommend the use of 100% softened makeup water for evaporative units which include any galvanized steel as part of the materials of construction. Split stream softening, which blends some percentage of raw (unsoftened) water with the softened water, may be a safe way to improve operating cycles of concentration.

Pros: Water softeners are easy to source and relatively inexpensive. The facility may already have a softener installed for steam boiler feedwater.

Cons: There is maintenance involved with a water softener. Salt must be regularly added to the brine tank to regenerate the resin. Brine is discharged during regeneration, and some municipal sewer authorities have regulated this discharge and limited new softener applications in their jurisdictions.

There is high water usage associated with the regeneration of the resin beds. This offsets a portion of the water savings gained from higher cycles of concentration. Hardness carryover or softener upsets can create a substantial risk of rapid scale formation in the evaporative cooling system.

Resin beds are sensitive to iron fouling, and carryover of high chloride concentrations following regeneration may increase corrosion potential in the evaporative cooling system.

Capacitive Deionization

Capacitive deionization technology captures a portion of the makeup water’s dissolved ion content, yielding a low-conductivity makeup water source for the evaporative cooling system. Makeup water entering the system passes through individual cylinders which contain oppositely charged supercapacitors. A portion of all the dissolved ions (except silica) are removed from the water. Operating at 50% ion reduction allows the operating cycles of concentration to be safely doubled without an increase in scale or corrosion potential.

Pros: This technology lowers energy consumption when compared to reverse osmosis (RO) systems. Upset conditions do not increase corrosion or scale potential like other pretreatment systems. Recovery rates range between 75% and 85%, which is higher than most RO systems. Capacitive deionization significantly reduces the amount of water treatment chemicals purchased, handled, stored, and discharged to treat the evaporative cooling system. These systems also provide improved water quality without the need to blend other water sources back in.

Link to CHT TECK

Cons: This technology does not reduce silica concentrations in areas where that is the limiting factor for water efficiency. They also require routine automated, or off-line, cleaning to maintain system efficiency.

Reverse Osmosis

RO is most often found in facilities requiring high-purity water for a process application. Makeup water is forced across a semi-permeable membrane, creating a high-purity stream and a concentrated brine waste stream. Re-using the concentrated brine stream is not recommended for an evaporative cooling system as it increases the potential for both corrosion and scale. A portion of the high-purity stream can be blended with the site’s makeup water to provide a lower conductivity makeup source for the evaporative system.

Pros: RO generates high-purity water that can be blended with raw water to create improved makeup water characteristics. It’s also effective at reducing all dissolved ions including silica concentration.

Cons: This technology comes with high energy consumption due to the need for supplemental pumping. Prefiltration and other pretreatments are often required. It also incurs a higher first cost when compared to other alternatives.

RO systems typically operate between 65% and 70% recovery, creating a meaningful waste stream. Neither 100% RO pure nor brine waters are appropriate for evaporative makeup due to corrosion and scale concerns.

Sodium zeolite softening, capacitive deionization, and reverse osmosis are pretreatment systems that have successfully been applied with evaporative cooling systems to increase operating cycles of concentration. Another chemical solution, which is not typically a pretreatment system, includes the feed of acid to reduce scaling potential by limiting the cycled alkalinity and pH in the recirculating water.

Acid Feed

Sulfuric acid is the most common acid used in evaporative cooling water treatment. Adding acid reduces both alkalinity and pH in the recirculating water. The primary reason this approach is utilized is the relatively low cost of the chemistry and feed equipment.

Like softening, however, the relatively low cost does not come without risk. Underfeeding or overfeeding of sulfuric acid can quickly create either scale or corrosion in an evaporatively cooled system. Therefore, site personnel should be actively engaged in the monitoring and testing of any pH control system operating on their evaporatively cooled system.

Experts recommend testing the site-specific makeup water early in the project design. This gives the end user a clear picture of their water efficiency and water treatment options. Testing water early on will also provide insight into whether upgrading materials of construction could improve ongoing water efficiency.

Advantages And Disadvantages of Water-Cooled Chillers

Chillers play an important role in many industries. They help keep medical machines running consistently, and they keep milk cool until it goes to markets. They assist in the pharmaceutical industry, the brewery industry, and in meat and poultry processing. If you’re looking for a chiller for your business, one of the things you’ll have to decide is whether you need an air-cooled chiller or a water-cooled chiller. To assist in your research, here are the main advantages and disadvantages of water-cooled chillers.

Advantages

Longer Lifespan

Water-cooled chillers usually don’t need replacement as often as air-cooled chillers do. They aren’t exposed to outdoor elements such as rain, snow, ice, and heat, which makes them less vulnerable.

Quiet Operation

While air-cooled chillers have ducts and vents that create noise, water-cooled chillers operate quietly. The flow of water through the system doesn’t result in the same noisy expansion and contraction that’s heard in air-cooled chillers. Quiet operation is particularly important in environments such as hospitals and schools, where noise can cause disturbance to occupants.

Energy Efficiency

The film coefficient is 10 to 100 times better in water-cooled chillers versus air-cooled chillers. This means that water-cooled chillers transfer heat more efficiently. The result to businesses is a savings on energy costs.

No Open Space Needed

Air-cooled chillers need to stay outdoors in an open space with plenty of fresh air to operate. Water-cooled chillers stay inside buildings, which makes them ideal for companies that don’t have access to enough outdoor space.

Safety

Water-cooled chillers use water as a refrigerant instead of toxic chemicals. This makes them safer for people who have contact with them.

Disadvantages

Higher Cost

Air-cooled chillers are cheaper than water-cooled chillers because they don’t require parts like cooling towers and condenser water pumps. Many companies feel that the longer lifespan and savings on energy costs make water-cooled chillers worth the initial high investment, however.

More Maintenance

Since water-cooled chillers have more parts, they require more maintenance. Companies should prepare to pay for periodic inspections, water treatments to remove impurities, and regular cleaning of the chiller’s machinery. More maintenance also means more downtime for the chiller. The more parts a machine has, the more things there are that can go wrong with the machine, which means water-cooled chillers are more likely to require repairs than air-cooled chillers.

Complicated Installation

The extra parts in water-cooled chillers also make installation more of a hassle. This can mean higher labor costs for installation of water-cooled chillers as opposed to air-cooled chillers.

Requires Mechanical Room

Businesses need to have a mechanical room to house a water-cooled chiller. This is to ensure that the chiller will function properly with its cooling tower and extra components.

Not Ideal For Drought-Stricken Areas

Since they use a good amount of water, water-cooled chillers aren’t great in regions that have water shortages. Companies that pay water costs can expect these bills to rise with the use of a water-cooled chiller. Some drought-stricken areas also have restrictions on water-cooled chiller use.

Less Efficient in Humidity

Although water-cooled chillers are overall more efficient than air-cooled chillers, they’ll operate less efficiently in humid environments. This is because humidity raises the wet-bulb temperature, which indicates how efficiently water absorbs heat. Water-cooled chillers in humid environments may also make building occupants feel cold and clammy.

Are you interested in learning more about Industrial Cooling System Manufacturers? Contact us today to secure an expert consultation!